Hydrants

Hydrant flow tests with the math done for you

Type the static, residual and flow readings. ExigentOps works out the rated flow at 20 psi and the NFPA 291 class and bonnet color while you type, and keeps every hydrant’s history.

NFPA 291 classes, calculated

Rated flow at 20 psi residual uses the standard formula, QR = QF × ((S − 20) ÷ (S − R))0.54, and the class follows from the result.

ClassRated flow at 20 psiBonnet color
AA1,500 gpm or moreLight blue
A1,000 to 1,499 gpmGreen
B500 to 999 gpmOrange
CUnder 500 gpmRed
  • GPS location from the phone with one tap, and an “Open in Maps” link on every hydrant.
  • Types for dry barrel, wet barrel, flush, dry hydrants and draft sites, and cisterns, with main size and owner.
  • Bulk import of up to 2,000 hydrants pasted from a spreadsheet, with bad rows flagged and duplicates skipped.
  • Service history for flow tests, inspections, flushing, repairs and painting.
  • Any member can mark a hydrant out of service with a reason. Only officers put it back.
  • Shows up in pre-plans, with each linked hydrant’s class color and out-of-service status.